IPS Deficiency Points

Code Description Point Max Point Rule Name Severity Days
A025 Administrative issues - see notes for specific details 15 15 R309-400-11 MIN 0
A050 Administrative issues - see notes for specific details 25 25 R309-400-11 SIG 120
A075 Administrative issues - see notes for specific details 50 50 R309-400-11 SIG 120
A100 Administrative issues - see notes for specific details 100 100 R309-400-11 SIG 120
A150 Administrative issues - see notes for specific details 200 200 R309-400-11 SIG 120
A200 ADMINISTRATIVE ISSUES - SEE NOTES FOR DETAILS 11(1) 25 100 ra test MIN 120
A225 System lacks permanent operating permit. See notes for details. 0 0 R309-500-9 (2) REC 0
A226 AFTER THE FACT OP ISSUED FOR FACILITY THAT DID NOT FOLLOW APPROVAL PROCESS. CODE REMAINS UNTIL FACILITY IS REPLACED OR UPDATED. 0 0 R309-500-6 REC 0
C001 SYSTEM DIRECT RESPONSIBLE CHARGE OPERATORS NOT CERTIFIED AT THE REQUIRED LEVEL 50 50 R309-105-11, R309-300-5(3) SIG 120
C002 OPERATOR NOT AVAILABLE WITHIN 1 HOUR TRAVEL TIME 0 0 R309-300-5(14) MIN 0
C003 OPERATOR CERTIFIED YET NOT REQUIRED 0 0 N/A REC 0
C004 OPERATOR CERTIFIED AT A HIGHER LEVEL THAN REQUIRED 0 0 R309-400-8(5) REC 0
C005 SYSTEM STAFF BFT CERTIFIED AS A CLASS I 0 0 TBD REC 0
C006 OPERATOR NOT CERTIFIED AT APPROPRIATE LEVEL 0 0 R309-300-19 MIN 0
C010 CERTIFIED IN DISCIPLINE NOT REQUIRED. 0 0 R309-400-8(5) REC 0
C011 TREATMENT PLANT NOT OPERATED BY OPERATOR CERTIFIED TO THE REQUIRED LEVEL 50 50 R309-525-7(3) SIG 120
COMT SURVEYOR COMMENT SEE NOTE SECTION FOR DETAILS 0 0 N/A REC 0
D001 DIST PIPING, FITTINGS OR MATERIAL NOT ANSI NSF 61 CERTIFIED 25 25 R309-550-6(1) & R309-550-6(3) SIG 120
D002 WATER LINES LACK REQUIRED MINIMUM SEPARATION FROM SEWER 25 25 R309-550-7 SIG 120
D003 DIST SYSTEM UNABLE TO PROVIDE 20 PSI MIN PRESSURE FOR WATER LINES CONSTRUCTED BEFORE JAN 1, 2007 50 50 R309-105-9, R309-550-5(1) SIG 120
D004 AIR RELIEF VALVE PIPE LACKS NO. 14 SCREEN 25 25 R309-550-6(6)(b) SIG 120
D005 A/V RELEASE VALVES SHOWS EVIDENCE OF FLOODING 0 0 TBD MIN 0
D006 AIR RELIEF VALVE PIPE NOT DOWNTURNED 25 25 R309-550-6(6)(b) SIG 120
D007 AIR RELIEF VALVE OR CHAMBER SUBJECT TO FLOODING 25 25 R309-550-6(6)(b) and (7)(b) SIG 120
D008 AIR OR VACUUM RELEASE VALVES FLOODED AT INSPECTION 0 0 R309-550-6(7)(b) MIN 0
D009 WATER MAINS SUSCEPTIBLE TO NEARBY CONTAMINATION SOURCES 50 50 R309-550-5(11) SIG 120
D010 DIST SYSTEM UNABLE TO PROVIDE 40 PSI DURING PEAK DAY AND 20 PSI DURING FIRE FLOW FOR WATER LINES INSTALLED AFTER JAN 2017 50 50 R309-105-9, R309-550-5(1) SIG 120
D011 INADEQUATE PROTECTION FOR DIST LINE CROSSING UNDER A SURFACE WATER BODY 25 25 R309-550-8(8)(b) SIG 120
D012 FIRE HYDRANT USE POLICY INADEQUATE 0 0 N/A REC 0
D013 DIST BLOWOFFS, FIRE HYDRANT, AIR RELIEF VALVE PIPING OR CHAMBER CONNECTED TO STORM DRAIN OR SANITARY SEWER 50 50 R309-550-6(5)(a), R309-550-6(6)(c) and (7)(a) SIG 120
D014 DIST PIPING AND FITTINGS INSTALLED AFTER JAN 2014 NOT LEAD FREE OR NOT ANSI NSF 372 OR 61G CERTIFIED 15 15 R30-550-6(2)(b) MIN 0
D015 DIST SYS WATER LINE AND SANITARY SEWER SEPARATION REQMTS NOT MET 0 0 R309-550-7 REC 0
D016 DIST SYS LINE CONNECTED TO OR SUBJECT TO CONTAMINATION 50 50 R309-550-9(1) and (2), R309-550-13(2) SIG 120
D017 INADEQUATE SAMPLE SITES FOR RESIDUAL TESTING 0 0 TBD MIN 0
D018 FAIL TO FOLLOW AWWA C651 FOR WATER LINE DISINFECTION 25 25 R309-550-8(10) SIG 120
D019 UNDERSIZED WATER MAIN SERVING FIRE HYDRANTS 15 15 R309-550-5(4) & (5) MIN 0
G001 UNAPPROVED FACILITY IN SERVICE 50 50 R309-100-5(2), R309-500-6, R309-500-9, R309-500-9(2) and (3) SIG 120
G003 SERVICE INTERRUPTIONS DUE TO POOR SYSTEM DESIGN 0 0 TBD REC 0
G004 INSUFFICIENT SYSTEM OWNERSHIP INFORMATION 15 15 R309-100-4(5) MIN 0
G005 NEW WATER SYTEM LACKS PLAN SUBMITTAL 0 0 TBD REC 0
G006 USING UNAPPROVED TREATMENT PROCESS OR CHEMICAL 50 50 R309-105-6(1)(a), R309-500-6 SIG 120
G007 CONSTRUCTION WITHOUT PRIOR APPROVAL 50 50 R309-100-5(1), R309-105-6(1)(a), R309-500-6, R309-500-9, R309-500-9(3) SIG 120
G07A CONSTRUCTION WITHOUT PRIOR APPROVAL 50 50 TBD SIG 120
G07B CONSTRUCTION WITHOUT PRIOR APPROVAL 50 50 TBD SIG 120
L009 WELL CASING DOES NOT EXTEND 18 IN ABOVE GROUND 0 0 TBD MIN 0
L011 WELL CASING NOT VENTED 0 0 TBD MIN 0
L012 NO PUMP TO WASTE LINE PRESENT 0 0 TBD MIN 0
L014 SPRING COLLECTION BOX NOT PRESENT 5 5 R309-515-7(7)(c) MIN 0
M000 OLD FINANCIAL MGMT PLAN IN PLACE 0 0 TBD MIN 0
M001 NO CURRENT EMERGENCY RESPONSE PROGRAM 0 0 R309-105-18 REC 0
M002 CURRENT FINANCIAL CAPACITY PLAN IN PLACE 0 0 TBD REC 0
M003 CCC-LACKS LOCAL AUTHORITY 15 15 R309-105-12(2) MIN 0
M004 CCC-NO ANNUAL PUBLIC EDUCATION OR AWARENESS 15 15 R309-105-12(2) MIN 0
M005 CCC-LACKS OPERATOR TRAINING 15 15 R309-105-12(2) MIN 0
M006 CCC-LACKS WRITTEN RECORDS OF CCC ACTIVITIES 15 15 R309-105-12(2) MIN 0
M007 CCC-LACKS ON-GOING ENFORCEMENT IMPLEMENTATION 15 15 R309-105-12(2) MIN 0
M008 SERVICE CONNECTIONS IN DISTRIBUTION SYSTEM RELY ON INDIVIDUAL HOME BOOSTER PUMP DUE TO INADEQUATE PRESSURE 50 50 R309-550-11(3) SIG 120
M009 IMPROPER BACTERIOLOGICAL SAMPLE COLLECTING AND HANDLING 15 15 R309-215-4(3) MIN 0
M010 WATER HAULING NOT ALLOWED FOR COMMUNITY SYSTEM 0 0 TBD REC 0
M011 UNAPPROVED WATER HAULING AS A SOURCE FOR COM SYSTEM 200 200 R309-550-10 SIG 120
M012 REC - WATER HAULING GUIDELINES MUST BE UTILIZED 0 0 R309-550-(1) MIN 0
M013 ENGINEERING EVALUATION REPORT 0 0 R309-400-12(3)(d) REC 0
M014 CONFIRMED PATTERN OF UNSATISFACTORY DRINKING WATER QUALITY SAMPLES 25 25 R309-200-6, R309-105-18, R309-215-4(3) SIG 120
M015 CONFIRMED WATER BORNE ILLNESS AS A RESULT OF PUBLIC DRINKING WATER CONTAMINATION 50 50 R309-105-18(f), R309-215-11 SIG 120
M016 HISTORY OF VERIFIED CUSTOMER COMPLAINTS REGARDING DRINKING WATER QUALITY OR QUANTITY 50 50 R309-105-18(f), R309-215-11 SIG 120
M017 WATER STAGNATION, BIOFILM OR SEDIMENTS CONTRIBUTES TO DRINKING WATER CONTAMINATION 50 50 R309-200-6, R309-105-18, R309-215-4(3) SIG 120
M018 INTERRUPTION OF TREATMENT PROCESS CONTRIBUTES TO DRINKING WATER CONTAMINATION 50 50 R309-200-6, R309-105-18, R309-215-5, R309-215-4(3) SIG 120
M019 FAILURE TO SUBMIT REQUIRED WATER USE DATA ANNUALLY OR VERIFY DATA ACCURACY 15 15 R309-105-15(1) MIN 0
M020 CROSS CONNECTION EXISTS IN WATER SYSTEM 50 50 R309-105-12(1) SIG 120
M021 INDIVIDUAL HOME BOOSTER PUMPS CONNECTED TO WATER MAIN DIRECTLY 50 50 R309-540-5(4)(c ), R309-550-11(3) SIG 120
M025 UNAPPROVED INTERCONNECTION WITH ANOTHER WATER SYSTEM 50 50 R309-550-9(3) SIG 120
M026 LACKS OPERATIONAL RECORDS 25 25 R309-105-14 SIG 120
M21A INDIVIDUAL HOME BOOSTER PUMPS CONNECTED TO WATER MAIN DIRECTLY 50 50 R309-550-11(3) SIG 120
PS00 WELL DISCHARGE PIPING EQUIP OUT OF ORDER 0 0 TBD MIN 0
PS01 PUMP FACILITY NOT PROTECTED FROM FLOODING OR SUFACE RUNOFF 15 15 R309-540-5(1)(a)(ii) and (iv) MIN 0
PS02 PS - NO CHECK VALVE ON DISCHARGE PIPING 0 0 TBD MIN 0
PS03 PUMP FACILITY LACKS PRESSURE GAUGE ON DISCHARGE LINE 15 15 R309-540-5 (6)(c)(i) MIN 0
PS04 PS - NO FLOW MEASURING DEVICE ON DISCHARGE PIPING 0 0 TBD REC 0
PS05 PUMP FACILITY LACKS SHUTOFF VALVES FOR O&M AND REPAIR 15 15 R309-540-5(6)(a) MIN 0
PS06 PUMP STATION BUILDING INTERIOR FLOOR NOT DRAINED OR NOT SLOPED TO DRAIN 15 15 R309-540-5(2)(a)(v) MIN 0
PS07 PUMP ELECTRICAL CONTROLS NOT PROTECTED AGAINST FLOODING 25 25 R309-540-5(6)(e) SIG 120
PS10 PUMP STATION OR HYDROPNEUMATIC TANK A/V VALVE RELIEF PIPING LACKS NO. 14 SCREEN 25 25 R309-550-6(6)(b), R309-540-6(2) SIG 120
PS11 A/V VALVE RELIEF PIPING OF PUMP STATION OR HYDROPNEUMATIC TANK NOT PROTECTED FROM CONTAMINATION OR NOT AT LEAST 6 INCHES ABOVE FLOOR 25 25 R309-550-6(6)(b), R309-540-6(2) SIG 120
PS12 PUMP STATION OR HYDROPNEUMATIC TANK A/V VALVE RELIEF PIPING NOT DOWNTURNED 25 25 R309-550-6(6)(b), R309-540-6(2) SIG 120
PS13 PUMP STATION BUILDING FLOOR ELEVATION NOT PROTECTED FROM FLOODING OR LESS THAN 6 INCHES ABOVE FINISH GRADE 15 15 R309-540-5(1)(a)(ii), R309-540-5(2)(a)(iii) MIN 0
PS14 PUMP STATION BUILDING NOT PROPERLY HEATED, LIGHTED OR VENTILATED 5 5 R309-540-5(2)(e ), (f) and (g) MIN 0
PS15 PUMP STATION HAS CROSS CONNECTION OR IS SUBJECT TO CONTAMINATION 50 50 R309-105-12(1) SIG 120
PS16 PS - NO GATES VLVS ON SUCTION & DISCHARGE OF PUMP 0 0 TBD REC 0
PS17 PS - PIPING OR APPURTENANCES LEAKING 0 0 N/A REC 0
PS18 IN-LINE BOOSTER PUMP STATION LACKS REDUNDANCY TO MEET PEAK DEMAND WITH ONE PUMP OUT OF SERVICE 25 25 R309-540-5(4)(b) SIG 120
PS19 PUMP FACILITY LACKS CAPACITY TO MEET DEMAND 25 25 R309-540-3(a) SIG 120
PS31 IMPROPER LUBRICATION OIL USED FOR DRINKING WATER PUMP FACILITY 25 25 R309-105-10(7) SIG 120
PS32 ELECTRICAL ROTATING EQUIP LACKS PROTECTIVE GUARDS 0 0 R309-545-19(1) REC 0
PS33 PUMP FACILITY NOT PROTECTED FROM VANDLISM OR UNAUTHORIZED ENTRY 15 15 R309-540-5(1)(a)(v) MIN 0
PS34 COM SYSTEM RELIES ON DIAPHRAGM OR AIR PRESSURE TANKS FOR FINISHED WATER STORAGE OR FIRE PROTECTION 15 15 R309-540-6(1) MIN 0
PSL1 NO MEANS TO RELEASE TRAPPED AIR FROM SOURCE PUMP 0 0 TBD MIN 0
PT01 HYDROPNEUMATIC TANK LACKS A BACK-UP PUMP 0 0 TBD MIN 0
PT02 HYDROPNEUMATIC TANK LACKS A BYPASS 0 0 TBD MIN 0
PT03 HYDROPNEUMATIC TANK LACKS AN ACCESS MANHOLE 0 0 TBD MIN 0
PT04 HYDROPNEUMATIC TANK LACKS A DRAIN 0 0 TBD MIN 0
PT05 HYDROPNEUMATIC TANK LACKS A PRESSURE GUAGE 0 0 TBD MIN 0
PT06 HYDROPNEUMATIC TANK LACKS A WATER SIGHT GLASS 0 0 TBD MIN 0
PT07 HYDROPNEUMATIC TANK LACKS AN AIR BLOW OFF 0 0 TBD MIN 0
PT08 HYDROPNEUMATIC TANK LACKS PRESSURE GAUGE 15 15 R309-540-6(3) MIN 0
PT09 HYDROPNEUMATIC TANK LACKS A MEANS TO ADD AIR 0 0 TBD MIN 0
PT10 HYDROPNEUMATIC TANK LACKS PRESSURE ON/OFF CONTROLS 0 0 TBD MIN 0
PT12 HYDROPNEUMATIC TANK HAS ANIMPROPER PUMP CYCLE 0 0 TBD MIN 0
PT13 HPUMP STATION/YDROPNEUMATIC TANK AND CONTROLS NOT PROTECTED AGAINST HAZARD 25 25 R309-540-5(1)(a)(i) SIG 120
PT14 HYDROPNEUMATIC TANK NOT PROTECTED FROM FLOODING 15 15 R309-540-6(2) MIN 0
R000 LACKS LEAD/COPPER SAMPLE SITE PLAN 0 0 TBD MIN 0
R001 INADEQUATE BACTERIOLOGICAL SAMPLING SITE PLAN 0 0 R309-211-4(1) MIN 0
R003 ASBESTOS CEMENT PIPE IN USE, MONITORING REQUIRED, REPLACEMENT RECOMMENDED 0 0 R30-550-6(2)(a) MIN 0
R004 NO ACCESS TO LAB OR TEST KITS FOR PROCESS TESTING 0 0 TBD REC 0
R005 EXPIRED CHEM REAGENT USED FOR PROCESS CONTROL TEST 0 0 TBD REC 0
R006 FAILURE TO MAKE THE LEAD SERVICE LINE INVENTORY PUBLICLY ACCESSIBLE 0 0 40 CFR 141.84 REC 0
S001 UNAPPROVED SOURCE IN SERVICE 200 200 R309-515-6(5), R309-515-7(4), R309-500-9(2) and (3) SIG 120
S002 WELL HOUSE NOT PROTECTED AGAINST VANDALISM 25 25 R309-105-10(5) SIG 120
S003 WELL CASING TERMINATES LESS THAN 12 INCHES ABOVE FLOOR OR LESS THAN 18 INCHES ABOVE GROUND SURFACE 25 25 R309-515-6(6)(b)(vi), R309-515-6(12)(c)(ii), R309-515-6(13)(a) SIG 120
S005 WELL WITH PITLESS ADAPTOR NOT WATER TIGHT OR NOT PROTECTED AGAINST VANDALISM 50 50 R309-515-6(12)(c) SIG 120
S006 END OF WELL CASING VENT LACKS NO. 14 SCREEN 25 25 R309-515-6(12)(d)(iii) SIG 120
S007 WELL CASING VENT IS NOT DOWNTURNED 25 25 R309-515-6(12)(d)(iii) SIG 120
S008 WELL CASING VENT LACKS PROPER AIR GAP AGAINST CONTAMINATION 25 25 R309-515-6(12)(d)(iii) SIG 120
S009 PUMP TO WASTE LINE LACKS PROPER AIR GAP 25 25 R309-515-6(12)(d)(ix) SIG 120
S010 END OF WELL PUMP-TO-WASTE LINE LACKS NO. 4 SCREEN 25 25 R309-515-6(12)(d)(ix) SIG 120
S011 WELL PUMP TO WASTE LINE NOT DOWNTURNED 25 25 R309-515-6(12)(d)(ix) SIG 120
S013 WELL LACKS THE REQUIRED WELL SEAL 50 50 R309-515-6(6)(i) SIG 120
S015 WELL LACKS A MEANS TO MEASURE WATER LEVELS PERIODICALLY 5 5 R309-515-6(12)(e ), R309-515-6(12)(c)(vi) MIN 0
S020 WELL HEAD OR WELL HOUSE NOT PROTECTED FROM FLOODING 25 25 R309-515-6(6)(b)(vi), R309-515-6(12)(d)(iii), R309-515-6(13)(a) to (d) SIG 120
S021 CROSS CONN EXISTS IN WELL HOUSE OR AT WELL HEAD 50 50 R309-105-12(1), R309-515-6(12)(d)(iii) SIG 120
S022 WELL HOUSE LACKS A MEANS OF PROVIDING DRAINAGE 5 5 R309-515-6(13)(b) MIN 0
S023 NO SMOOTH NOSED SAMPLING TAP ON DISCHARGE PIPING 5 5 R309-515-6(12)(d)(iv) MIN 0
S024 NO CHECK VALVE ON WELL DISCHARGE PIPING 5 5 R309-515-6(12)(d)(iv) MIN 0
S025 NO PRESSURE GAUGE ON WELL DISCHARGE PIPING 5 5 R309-515-6(12)(d)(iv) MIN 0
S026 NO FLOW METER ON WELL DISCHARGE PIPING 5 5 R309-515-6(12)(d)(iv) MIN 0
S027 NO SHUT OFF VALVE ON WELL DISCHARGE PIPING 5 5 R309-515-6(12)(d)(iv) MIN 0
S028 AIR RELEASE VACUUM RELIEF VALVE PIPING NOT DOWNTURNED 25 25 R309-515-6(12)(d)(v) SIG 120
S029 END OF AIR RELEASE VACUUM RELIEF VALVE PIPING LACKS NO. 14 SCREEN 25 25 R309-515-6(12)(d)(v) SIG 120
S030 END OF AIR RELEASE VACUUM RELIEF VALVE PIPING LACKS A CLEARANCE OF AT LEAST 6 INCHES 25 25 R309-515-6(12)(d)(v) SIG 120
S031 PUMP LUBRICANTS NOT FOOD GRADE MINERAL-OIL 25 25 R309-105-10(7), R309-515-6(6)(a) SIG 120
S032 ELECTRICAL ROTATING EQUIP LACKS PROTECTIVE GUARDS 0 0 TBD REC 0
S033 COM SYSTEM WITHOUT NATURALLY FLOWING SOURCES LACKS BACKUP POWER FOR AT LEAST ONE WATER SOURCE 25 25 R309-515-6(2)(a) SIG 120
S090 SYSTEM LACKS UP TO 20% OF REQUIRED SOURCE CAPACITY 15 15 R309-510-7 MIN 0
S091 SYSTEM LACKS UP TO 20% OF REQUIRED SOURCE CAPACITY 15 15 R309-510-7(1) MIN 0
S092 SYSTEM LACKS MORE THAN 20% OF REQUIRED SOURCE CAPACITY 50 50 R309-510-7 SIG 120
S093 SYSTEM LACKS MORE THAN 20% OF REQUIRED SOURCE CAPACITY 50 50 R309-510-7 SIG 120
S094 SYSTEM LACKS MORE THAN 20% OF REQUIRED SOURCE CAPACITY 50 50 R309-510-7(1) SIG 120
S095 UNFINISHED WELL NOT CAPPED SECURELY 50 50 R309-515-6(8)(a), R655-4-14.1 SIG 120
S096 COMMUNITY WATER SYSTEM (WITHOUT NATURALLY FLOWING WATER SOURCE) LACKS AT LEAST ONE REDUNDANT POWER SOURCE 0 0 R309-515-6(2)(a) REC 0
S097 SURFACE WATER/UDI SOURCE LACKS SURFACE WATER TREATMENT 0 0 R309-515-5(1) & 7(1) MIN 0
S150 GWUDI OR SURFACE WATER SOURCE LACKS SURFACE WATER TREATMENT 200 200 R309-505-5(1)(a) to (d), R309-505-7(1), R515-7(3), R309-520-6(3)(a) and (4) SIG 120
SL01 WELL THAT PUMPS DIRECTLY TO DISTRIBUTION LACKS A MEANS TO RELEASE TRAPPED AIR 5 5 R309-515-6(12)(d)(v) MIN 0
SP01 PER FOR ACTIVE SOURCE NOT UPGRADED TO FULL DWSP 0 0 R309-600-5 & 605-6(h) REC 0
SP02 PER NOT UPGRADED TO FULL DWSP PLAN 25 25 R309-600-13(6) & R309-605-9(3) SIG 120
SP03 DWSP PLAN NOT IMPLEMENTED ACCORDING TO MANAGEMENT STRATEGIES IN DWSP 25 25 R309-600-7(2)(d) & R309-605-7(1)(c)(iv) SIG 120
SP04 ACTIVE SOURCE LACKS APPROVED UPDATES TO DWSP PLAN 5 5 R309-600-7(2)(e) & R309-605-7(c)(v) MIN 0
SP05 NO DOCUMENTED LAND MANAGEMENT STRATEGIES ON FILE 0 0 TBD REC 0
SP06 NEW WATER SOURCE LACKS APPROVED PER 50 50 R309-600-13 & R309-605-9 SIG 120
SP07 ACTIVE SOURCE LACKS AN APPROVED DWSP PLAN 25 25 R309-600-7(2) & R309-605-7(1)(c) SIG 120
SP08 OLD SOURCE LACKS A DWSP PLAN 0 0 R309-600 7(1) REC 0
SP09 REDEVELOPED SOURCE LACKS A REVISED DWSP PLAN 15 15 R309-600-7(2)(f) & R309-605-7(1)(c)(vi) MIN 0
SS01 LACKS A PERMANENT DEVICE FOR MEASURING SPRING FLOW 5 5 R309-515-7(7)(h) MIN 0
SS02 SPRING COLLECTION AREA NOT FENCED 15 15 R309-515-7(7)(e) MIN 0
SS03 SPRING LACKS A DIVERSION CHANNEL OR BERM TO DIVERT RUNOFF AWAY FROM SPRING COLLECTION AREA 15 15 R309-515-7(7)(g) MIN 0
SS04 SPRING BOX OVERFLOW LACKS NO. 4 SCREEN 25 25 R309-515-7(7)(d), R309-545-13(3) SIG 120
SS05 PONDING WITHIN SPRING COLLECTION AREA 25 25 R309-515-7(7)(i) SIG 120
SS06 PONDING WITHIN SPRING COLLECTION AREA 25 25 R309-515-7(7)(i) SIG 120
SS07 DEEP ROOTED VEGETATION IN SPRING COLLECTION AREA 25 25 R309-515-7(7)(f) SIG 120
SS08 ROOTS IN SPRING COLLECTION PIPES 25 25 R309-105-10(4)(a), R309-515-8(1)(a) SIG 120
SS09 SPRING BOX LID NOT SHOEBOX STYLE 25 25 R309-515-7(7)(d), R309-545-14 (2) SIG 120
SS10 SPRING BOX LID LACKS A GASKET 25 25 R309-515-7(7)(d), R309-545-14 (2) SIG 120
SS11 SPRING BOX LACKS A MEANS OF VENTING 5 5 R309-515-7(7)(d), R309-545-15 MIN 0
SS12 SPRING BOX ENTRY NOT ELEVATED AT LEAST 18 INCHES ABOVE EARTHEN COVER 15 15 R309-515-7(7)(d), R309-545-14 (1), MIN 0
SS13 SPRING BOX LID IS NOT LOCKED 25 25 R309-515-7(7)(d), R309-545-14 (3) SIG 120
SS14 SPRING BOX OVERFLOW OR DRAIN LACKS FREE FALL OF 12 TO 24 INCHES 25 25 R309-515-7(7)(d), R309-545 SIG 120
SS15 HEIGHT OF SPRING BOX VENT NOT SIZED TO PREVENT BLOCKAGE IN WINTER 25 25 R309-515-7(7)(d), R309-545-15(3) SIG 120
SS16 SPRING BOX VENT NOT DOWNTURNED 25 25 R309-515-7(7)(d), R309-545-15(1) SIG 120
SS17 SPRING BOX VENT LACKS NO. 14 SCREEN 25 25 R309-515-7(7)(d), R309-545-15(4) and (5) SIG 120
SS18 END OF SPRING BOX VENT IS AT LEAST 24 INCHES ABOVE EARTHEN COVER 25 25 R309-515-7(7)(d), R309-545-15(2) and (3) SIG 120
SS19 SPRING IMPERMEABLE LINER INADEQUATE OR NOT INTACT 50 50 R309-515-7(7)(b)(iv) SIG 120
SS20 UNSEALED OPENINGS IN SPRING COLLECTION BOX 50 50 R309-515-7(7)(d), R309-545-9(1) and (2) SIG 120
SS21 DRAIN LINE DOES NOT HAVE ADEQUATE AIR GAP NOT COVERED IN IPS 0 0 R309-515-7(7)(d) MIN 0
SS22 SPRING IMPERVIOUS SOIL COVER INADEQUATE OR NOT INTACT 50 50 R309-515-7(7)(b) SIG 120
SS23 SPRING BOX LACKS A MEANS OF PROVIDING OVERFLOW 15 15 R309-515-7(7)(d), R309-545-13(1) MIN 0
SS24 HERBICIDE, PESTICIDES OR ALGICIDES APPLIED ARE NOT ANSI NSF 60 CERTIFIED AND WITHOUT APPROVAL 50 50 R309-105-10(4)(b), R309-515-8(1)(b) and (3) SIG 120
SSL1 PONDING OF WATER OR DRAINAGE AROUND SPRING 0 0 TBD 0
SSL2 VENT NOT PRESENT 0 0 R309-515-7(7)(d) MIN 0
SW01 NO LID OVER GALLERY 0 0 TBD REC 0
SW02 GALLERY LID IS NOT WATER TIGHT OR LOCKED 0 0 TBD REC 0
SW03 COLLECTOR IS NOT MAINTAINED & IN DISREPAIR 0 0 TBD REC 0
SW04 INTAKE AREA NOT FREE OF CONTAMINATION 0 0 TBD REC 0
SW05 INTAKE AREA NOT RESTRICTED 0 0 TBD REC 0
T001 PLANT LACKS PROVISION FOR BYPASSING PRESEDIMENTATION BASINS 15 15 R309-525-10(3) MIN 0
T002 PRIMARY COAGULANT NOT USED PROPERLY 50 50 R309-525-11(1)(a) SIG 120
T003 NO PLAN TO DETERMINE COAGULANT DOSAGE 0 0 TBD MIN 0
T004 FILTRATION BASINS LACK SAFETY HANDRAILS 25 25 R309-525-15(6)(n) SIG 120
T005 MULTI-MEDIA FILTER NOT PROVIDED WITH CONTINUOUS TURBIDITY MONITORING 50 50 R309-525-15(4)(b)(vi), R309-525-15(4)(c)(vii) SIG 120
T006 NO SAMPLE TAP OR MEANS TO SAMPLE RAW WATER OR FINISHED WATER 25 25 R309-525-15(10)(a)(i) SIG 120
T007 NO MEANS TO MONITOR MEDIA FILTER HEAD LOSS 25 25 R309-525-15(10)(a)(ii) SIG 120
T008 NO MEANS TO MONITOR OR RECORD FLOW RATE OF EACH FILTER 15 15 R309-525-15(10)(a)(iii), R309-525-15(2) MIN 0
T009 SLOW SAND PROCESS DOES NOT HAVE AT LEAST 3 FILTER UNITS 15 15 R309-530-6(5)(a) MIN 0
T010 FLOCCULATORS DO NOT HAVE VARIALBLE SPEED CONTROL 0 0 TBD MIN 0
T011 NO BAFFLING UTILIZED TO ENHANCE FLOC FORMATION 0 0 TBD MIN 0
T012 DETENTION TIME IS LESS THAN 30 MIN FOR FLOC FORM 0 0 TBD MIN 0
T013 FLOW THRU VELOCITY <.5 OR >1.5 FEET PER MINUTE 0 0 TBD MIN 0
T014 NO SOP FOR ADJUSTING FLOCCULATOR SPEED 0 0 TBD MIN 0
T015 NO MEANS TO DEWATER OR REMOVE SLUDGE 0 0 TBD MIN 0
T016 INLET/OUTLET DESIGN PROMOTES SHORT CIRCUITING 0 0 TBD MIN 0
T017 EVIDENCE OF SHORT CIRCUITING IN FLOC FORMATION 0 0 TBD MIN 0
T018 CLEAR WELL LACKS AN OVERFLOW AND VENT 25 25 R309-525-16(1)(b)(iii), R309-545 SIG 120
T019 LACKS SUFFICIENT LABORATORY EQUIPMENT FOR PROPER O&M OF THE PLANT 25 25 R309-525-17(1) SIG 120
T020 FILTERS NOT OPERATED TO MINIMIZE FLOW VARIATIONS 0 0 TBD MIN 0
T021 INSTRUMENTATION AND CONTROLS IN TREATMENT PLANT NOT MAINTAINED, OPERABLE, OR FUNCTIONING PROPERLY 25 25 R309-100 - R309-600 SIG 120
T022 NO SAMPLE TAP PRIOR TO PERMANGANATE APPLICATION 0 0 TBD MIN 0
T023 NO SAMPLE TAP AT FILTER EFFLUENT 0 0 TBD MIN 0
T024 MEDIA DEPTHS NOT PERIODICALLY CHECKED TO DESIGN 0 0 TBD MIN 0
T025 NO SOP FOR BACKWASH PROCEDURE 0 0 TBD MIN 0
T026 NO FILTER TO WASTE AFTER A BACKWASH 0 0 TBD MIN 0
T027 IN-PLANT WATER SUPPLY TO LABORATORY AND SANITARY FACILITIES NOT OF FINISHED WATER QUALITY 25 25 R309-525-16, R309-525-17(3) SIG 120
T028 INCORRECT COMPLIANCE CHLORINE RESIDUAL SAMPLING LOCATION 25 25 R309-215 SIG 120
T029 CHEMCIAL DOSING NOT PROPORTIONAL TO FLOW CHANGES 15 15 R309-525-11(7)(d)(ii) MIN 0
T030 NO PRETREATMENT TO PREVENT RAPID FOULING 0 0 TBD MIN 0
T031 NO DISINFECT USD-REDUCE FOULING/MICROBIAL PAS THRU 0 0 TBD MIN 0
T032 OPERATING FILTER ABOVE APPROVED LOADING RATE 15 15 R309-105, R309-525-15(2), R309-525-15(4)(a), R309-525-15(4)(b)(v), R309-525-15(4)(c)(vi), R309-525-15(2), R309-530 MIN 0
T033 MEDIA DEPTHS NOT MEETING REQUIREMENTS 25 25 R309-525-15(4) SIG 120
T040 NO CONTINUOUS FLOW TO FILTERS 0 0 TBD MIN 0
T041 PRECOAT THICKNESS LESS THAN 1/8 INCH 0 0 TBD MIN 0
T042 CONT BODY FEED NOT BEING USED 0 0 TBD MIN 0
T043 FILTER OR MEDIA NOT CLEANED, INSPECTED, MAINTAINED OR PROPERLY FUNCTIONING 25 25 R309-105-10, R309-525-19, R309-525-15(4)(a), R309-525-15(4)(b)(ii to v), R309-525-15(4)(c)(ii to vi) SIG 120
T044 FILTER SEPTUM NOT REGULARLY CLEANED 0 0 R309-530-7 REC 0
T050 MEDIA DEPTHS NOT PERIODICALLY CHECKED TO DESIGN 0 0 TBD MIN 0
T051 NO SOP FOR BACKWASH PROCEDURE 0 0 TBD MIN 0
T052 NO FILTER TO WASTE AFTER A BACKWASH 0 0 TBD MIN 0
T053 SYSTEM STARTS ON DIRTY FILTERS 0 0 TBD SIG 0
T060 NO MEANS TO ACCURATELY MEASURE FLOW TO EACH FILTER 0 0 TBD MIN 0
T061 INADEQUATINADEQUATE SAMPLE TAPS AT EACH FILTER 0 0 TBD MIN 0
T063 FILTER NOT RIPENED BEFORE PUT INTO SERVICE 0 0 TBD SIG 0
T071 INADEQUATE MONITORING TO PREVENT PREMATURE FOULING 0 0 TBD MIN 0
T072 UNIT IS NOT PROPERLY SEALED TO PREVENT LEAKAGE 0 0 TBD MIN 0
T073 INADEQUATE MONITORING TO INSURE MEMBRANE INTEGRITY 0 0 TBD MIN 0
T074 NO FILTER-TO-WASTE PROVISION FOR EACH FILTER 25 25 R309-525-15(6)(p) SIG 120
T075 BACKWASH WATER SUPPLYNOT OF FINISHED DRINKING WATER QUALITY 50 50 R309-525-15(7)(a)(ix) SIG 120
T076 INADEQUATE WATER SUPPLY OR FLOW RATE TO MEET FILTER BACKWASH NEEDS 15 15 R309-525-15(7) MIN 0
T077 BACKWASH TANK DOES NOT PERFORM IN CONJUNCTION WITH FILTER TO WASTE SYSTEM 0 0 R309-525-15-(7)(a)(xi) REC 0
T080 CHEMICALS USED FOR DRINKING WATER TREATMENT NOT ANSI NSF 60 CERTIFIED 25 25 R309-525-11(5), R309-525-25(1), R309-535-11(5)(d) SIG 120
T081 FLASH MIX PROCESS FUNCTIONS IMPROPERLY OR CHEMICAL FOR FLASH MIXING ADDED IMPROPERLY 15 15 R309-525-12(1) MIN 0
T082 FLOCCULATION PROCESS FUNCTIONS IMPROPERLY 15 15 R309-525-12(2)(g) MIN 0
T083 NO MEANS TO DETERMINE ANTICIPATED COAGULANT DOSE 15 15 R309-525-11(2)(a) and (d) MIN 0
T084 REQUIRED DISINFECTANT NOT ADDED TO FINISHED WATER 50 50 R309-525-11(1)(b) SIG 50
T085 MULTI-MEDIA FILTER NOT EQUIPPED TO INITIATE AUTOMATIC SHUTDOWN OR BACKWASH 50 50 R309-525-15(4)(b)(vi), R309-525-15(4)(c)(vii) SIG 120
T086 SLOW SAND FILTERS ARE NOT PROTECTED TO PREVENT FREEZING 15 15 R309-530-6(5)(b) MIN 0
T087 SLOW SAND FILTERS DO NOT HAVE AT LEAST 24 INCHES OF SAND THAT MEETS RULE REQUIREMENTS 15 15 R309-530-6(5)(e ) and (f) MIN 0
T088 SLOW SAND FILTERS ARE NOT MAINTAINED OR OPERATED PROPERLY 15 15 R309-530-6(5)(c) MIN 0
T089 SLOW SAND FILTERS DOES NOT HAVE FILTER-TO-WASTE PROVISION 25 25 R309-530-6(5)(k) SIG 120
T090 SOURCE WATER QUALITY OR TURBIDITY UNSUITABLE FOR SLOW SAND TREATMENT 50 50 R309-530-6(2)(a) SIG 120
T091 INADEQUATE DIRECT INTEGRITY TESTING TO MONITOR MEMBRANE INTEGRITY FOR EACH MEMBRANE UNIT 50 50 R309-215-15(18)(b)(iii) SIG 120
T092 INADEQUATE CONTINUOUS INDIRECT INTEGRITY TESTING TO MONITOR MEMBRANE INTEGRITY FOR EACH UNIT 50 50 R309-215-15(18)(b)(iv) SIG 120
T093 INCORRECT CONTROL LIMIT OF MEMBRANE DIRECT INTEGRITY TEST SENSITIVITY TO INDICATE LOG REMOVAL 50 50 R309-215-15(18)(b)(iii)(D) SIG 120
T094 INCORRECT TRIGGER FOR MEMBRANE CONTINUOUS INDIRECT INTEGRITY TESTING 50 50 R309-215-15(18)(b)(iv) SIG 120
T095 INSUFFICIENT BACKWASH WATER SUPPLY TO ALLOW BACKWASHING 2 MEMBRANE UNITS CONSECUTIVELY 15 15 R309-525-15(7)(a)(iv) MIN 0
T096 CLEAR WELL INADEQUATELY DESIGNED TO PROVIDE REQUIRED DISINFECTION CT 25 25 R309-525-16(b) and (b)(i) SIG 120
T097 LACKS MONITORING OR RECORDS OF RECYCLED WATER 15 15 R309-215-8(1) MIN 0
T098 FAIL TO MEET GIARDIA, VIRUS OR CRYPTOSPORIDIUM TREATMENT REQUIREMENTS 100 100 R309-505-5(1)(d), R309-215 SIG 120
T099 INCORRECT SURFACE WATER TREATMENT COMPLIANCE WATER QUALITY SAMPLING LOCATION 25 25 R309-215 SIG 120
TA01 AERATOR SHOWS SIGNIFICANT CORROSION 0 0 TBD MIN 0
TA02 NO PERIODIC MAINTENANCE ON AERATOR 0 0 TBD 0
TC01 ACTIVATED CARBON MEDIA DEPTHS NOT CHECKED 0 0 TBD REC 0
TC02 ACTIVATED CARBON NO SOP FOR BACKWASH 0 0 TBD REC 0
TC03 ACTIVATED CARBON - NO FILTER TO WASTE PRACTICED 0 0 TBD REC 0
TC04 ACTIVATED CARBON - SYSTEM STARTS ON DIRTY FILTERS 0 0 R309-525-25(3) REC 0
TC05 ACTIVATED CARBON - PAC IS NOT ADD AS EARLY AS POSS 0 0 TBD MIN 0
TC06 ACTIVATED CARBON - IS NOT PROPERLY WETTED 0 0 TBD MIN 0
TC07 ACTIVATED CARBON APPLICATION POINT NOT APPROPRIATE (BEFORE OXIDANT ADDITION) 15 15 R309-525-11(2)(a) and (d) MIN 0
TC08 ACTIVATED CARBON - PAC ADD IS NOT AT MULTIPLE PTS 0 0 TBD MIN 0
TC09 ACTIVATED CARBON - FEED INSTALL NOT IN SEPARATE RM 0 0 TBD MIN 0
TC10 ACTIVATED CARBON NOT STORED SEPARTELY OR AWAY FROM INCOMPATIBLE CHEMICALS 25 25 R309-525-11(7)(a)(iv), R309-105-10 SIG 120
TC11 ACTIVATED CARBON - PAC NOT HANDLED AS COMBUSTIBLE 0 0 TBD MIN 0
TC12 ACTIVATED CARBON - NO XCON CONTROL IN TRTMT PLANT 0 0 TBD MIN 0
TC13 ACTIVATED CARBON - HOSEBIBB XCON UNPROTECTED 0 0 TBD MIN 0
TC14 ACTIVATED CARBON - CHEM FEED PUMP OUTPT INADEQUATE 0 0 TBD MIN 0
TC15 PIPING NOT COLOR CODED OR LABLED TO INDICATE CONTAINED LIQUID AND FLOW DIRECTION 5 5 R309-525-8 MIN 0
TC16 ACTIVATED CARBON - PLANT WATER SUPPLY INADEQUATE 0 0 TBD REC 0
TC17 ACTIVATED CARBON STORAGE AND OPERATION AREA NOT CLEAN, DRY OR SAFE FOR OPERATOR SAFETY 25 25 R309-525-11(6)(a)(i)(C ), R309-525-11(6)(c ), R309-525-19, R309-105-10, R309-525-15(d) SIG 120
TC18 ACTIVATED CARBON - PLANT EQUIP VENTING INADEQUATE 0 0 R309-520-10(2)(f) REC 0
TC19 ACTIVATED CARBON - UNTRAINED OPERATORS ON PROCESS 0 0 TBD REC 0
TC20 ACTIVATED CARBON - LACK OF 30 DAY CHEMICAL SUPPLY 0 0 TBD MIN 0
TD01 CONTINUOUS DISINFECTION IS REQUIRED BUT CHLORINATOR LACKS AUTOMATIC SWITCHOVER 15 15 R309-520-7(2)(a), R309-520-6(1) MIN 0
TD02 LACKS EQUIPMENT TO MEASURE CHLORINE FEED RATE 25 25 R309-520-7(2)(i) SIG 120
TD03 CL2 - NO SHUT OFF VALVE ON INJECTOR PIPING 0 0 TBD REC 0
TD04 150-POUND CYLINDER FACILITY LACKS IMMEDIATE ACCESS TO NIOSH RESPIRATOR 25 25 R309-520-7(2)(k)(ii) SIG 120
TD05 1-TON CYLINDER FACILITY LACKS A LEAK REPAIR KIT APPROVED BY CHLORINE INSTITUTE 25 25 R309-520-7(2)(l)(ii) SIG 120
TD06 1-TON CYLINDER FACILITY LACKS IMMEDIATE ACCESS TO IOSH SELF-CONTAINED BREATHING APPARATUS 25 25 R309-520-7(2)(k)(i) and (ii) SIG 120
TD07 GAS CHLORINE AREA IN TREATMENT PLANT NOT SEPARATE FROM OTHER AREAS 25 25 R309-520-7(2)(g)(v) SIG 120
TD08 CHLORINATOR BUILDING NOT HEADED, LIGHTED OR VENTILATED 15 15 R309-520-7(1)(l) MIN 0
TD09 CHLORINE ROOM EXHAUST FAN SUCTION NOT LOCATED NEAR FLOOR 15 15 R309-520-7(2)(d)(iii) MIN 0
TD10 CHLORINE ROOM AIR INLET NOT LOCATED NEAR CEILING THROUGH WALL LOUVERS 15 15 R309-520-7(2)(d)(iv) MIN 0
TD11 CL2 LOUVERS FOR AIR INTAKE / EXHAUST NOT AIRTIGHT 0 0 TBD REC 0
TD12 LACK SEPARATE SWITCHES FOR FAN AND LIGHTS NEAR CHLORINE ROOM ENTRANCE 15 15 R309-520-7(2)(d)(v) MIN 0
TD13 CHLORINE VENT LINE NOT DISCHARGED OUTSIDE ABOVE GRADE OR LACKS NO. 14 SCREEN 25 25 R309-520-7(2)(e) SIG 120
TD14 NO AMMONIA HYDROXIDE SOLUTION FOR CHLORINE LEAK DETECTION 15 15 R309-520-7(2)(l)(i) MIN 0
TD15 CHLORINE CYLINDERS NOT RESTRAINED 25 25 R309-520-7(2)(h) SIG 120
TD16 INADEQUATE DISINFECTION FOR GROUND WATER SOURCE REQUIRED TO DISINFECT 200 200 R309-520-6(3)(b) and (4) SIG 120
TD17 CHLORINE CYLINDERS ARE EXPOSED TO DIRECT SUN OR EXCESSIVE HEAT 25 25 R309-520-7(2)(f)(ii) SIG 120
TD18 1-TON CYLINDER CHLORINE ROOM VENTILATION NOT INDEPENDENT OR SEPARATE FROM VENTILATION FOR THE REST OF THE TREATMENT PLANT 25 25 R309-520-7(2)(d)(iv) SIG 120
TD19 1-TON CYLINDER FACILITY LACKS CONTINUOUS CHLORINE LEAK DETECTION EQUIPMENT 25 25 R309-520-7(2)(l)(iii) SIG 120
TD20 CL2 NO PRESSURE GUAGE AT IN/OUT OF INJECTOR 0 0 TBD REC 0
TD21 CROSS CONNECTION EXISTS IN CHLORINE MAKEUP WATER SUPPLY LINE 25 25 R309-520-7(1)(h)(i) SIG 120
TD22 LACKS BACKUP POWER SUPPLY FOR REQUIRED DISINFECTION 25 25 R309-520-7(1)(k)(ii) SIG 25
TD23 1-TON CYLINDER FACILITY LACKS ALARMS ON CONTINOUS CHLORINE LEAK DETECTOR 25 25 R309-520-7(2)(l)(iv) SIG 120
TD24 HYPOCHLORITE TANK LACKS LIQUID LEVEL INDICATOR 5 5 R309-525-11(6)(a)(iv)(A) MIN 0
TD25 DISINFECTION IS REQUIRED BUT DISINFECTION IS INTERMITTENT OR NOT CONTINUOUS 50 50 R309-520-6 SIG 120
TD26 FAIL TO PROVIDE DISINFECTION CT OR REPORT INACCURATE CT FOR REQUIRED TREATMENT 50 50 R309-505-7(2), R309-520-4 and 6(4) SIG 120
TD27 CL2 INCORRECT REAGENT USED FREE RESIDUAL TEST 0 0 TBD REC 0
TD28 COMBUSTIBLE OR REACTIVE MATERIALS STORED IN CHLORINE DIOXIDE OPERATING AREA 50 50 R309-520-10(5)(a) SIG 120
TD29 HYPOCHLORITE FACILITY DOES NOT HAVE ADEQUATE SPILL CONTAINMENT 5 5 R309-525-11(6)(a)(iv)(B) MIN 0
TD30 PERSONAL PROTECTIVE EQUIPMENT NOT AVAILABLE NEAR AND OUTSIDE OF CHLORINE DIOXIDE OPERATING AREA 25 25 R309-520-10(5)(c) SIG 120
TD31 CHLORINE DIOXIDE FACILITY LACKS EMERGENCY EYEWASH AND SAFETY SHOWER 25 25 R309-520-10(3)(b)(viii) SIG 120
TD32 NO EMERGENCY SHUTOFF FOR CHLORINE DIOXIDE GENERATOR 25 25 R309-520-10(3)(b)(ix) SIG 120
TD33 CHLORINE DIOXIDE OPERATING AREA AND SOLUTION TANKS NOT PROPERLY VENTED 15 15 R309-520-10(3)(b)(xi) MIN 0
TD34 NO AMBIENT CHLORINE DIOXIDE SENSOR OR ALARM OR WARNING LIGHT 25 25 R309-520-10(3)(b)(v) SIG 120
TD35 CHLORINE DIOXIDE OPERATING AREA LACKS WASH DOWN WATER 15 15 R309-520-10(3)(b)(xvi) MIN 0
TD36 CHLORINE DIOXIDE OPERATING AREA TEMPRATURES NOT MAINTAINED BETWEEN 60 AND 100 DEGREES F 15 15 R309-520-10(5)(d) MIN 0
TD37 CHLORINE DIOXIDE FACILITY LACKS SAFETY AND EMERGENCY MANUAL OR OPERATORS LACKS SAFETY AND EMERGENCY TRAINING 25 25 R309-520-10(5)(f) SIG 120
TD38 NO SAFETY AND EMERGENCY TRAINING 0 0 R309-520-10(5)(f) MIN 0
TD39 UV FACILITY LACKS STANDARD OPERATING PROEDURES 15 15 R309-520-8(4)(b) MIN 0
TD40 UV INTENSITY SENSOR NOT CORRECTLY CALIBRATED 0 0 R309-520-8(4) REC 0
TD41 CLEANING CHEMICALS DO NOT MEET ANSI NSF 60 STANDARD 50 50 R309-520-8(3)(j) SIG 120
TD42 UNABLE TO ISOLATRE UV REACTOR FOR MAINTENANCE 15 15 R309-520-8(3)(g) MIN 0
TD43 LACKS BACKUP POWER SUPPLY FOR REQUIRED UV DISINFECTION 25 25 R309-520-8(3)(l) SIG 120
TD44 LACKS REDUNDANT PRIMARY DISINFECTION METHOD IF UV REACTOR IS OFF SPEC 25 25 R309-520-8(3)(m) SIG 120
TD46 OZONE FACILITY LACKS ADEQUIATE OZONE RESIDUAL ANALYZERS FOR CT DETERMINATION 15 15 R309-520-9(7)(c) MIN 0
TD47 QUENCHING CHEMICALS DO NOT MEET ANSI NSF 60 STANDARD 50 50 R309-520-9(4)(h) SIG 120
TD48 OZONE OFF-GAS BLOWERS NOT FUNCTIONING 15 15 R309-520-9(5)(b) MIN 0
TD49 OZONE OFFGAS DISTRUCTION UNITS NOT PROVIDED OR NOT FUNCTIONING 15 15 R309-520-9(5)(a) MIN 0
TD50 OZONE OFF-GAS DESTRUCTION NOT LESS THAN 0.1 PPM 0 0 R309-520-9(5)(d) MIN 0
TD51 CL2 HYPO FEEDERS ARE NOT POS. DISPLACEMNT TYPE 0 0 TBD REC 0
TD52 CL2 UNPROTECTED CROSS CONN PRESENT IN FEED LINE 0 0 R309-525-11(9)(c) REC 0
TD53 CL2 UNPROTECTED CROSS CONN PRESENT ON DRAIN 0 0 TBD MIN 0
TD54 HYPOCHLORITE SYS TANKS NOT PROPERLY LABELED 0 0 R309-525-11(8)(c)(vii) MIN 0
TD55 CL2 OVERFLOW PIPE HIDDEN FROM VIEW 0 0 TBD REC 0
TD56 GAS CHLORINE ROOM IN TREATMENT PLANT LACKS SHATTER RESISTANT INSPECTION WINDOW(S) 25 25 R309-520-7(2)(g)(i) SIG 120
TD57 VENTILATION NOT SEPARATE FROM REST OF TREATMENT PLANT 0 0 R309-520-7(2)(d)(vi) REC 0
TD58 STANDBY POWER NOT AVAILABLE FOR PRIMARY TREATMENT PROCESSFOR SURFACE WATER TREATMENT 25 25 R309-525-7(5), R309-525-11(7)(b)(iii) SIG 120
TD59 BACKUP EQUIPMENT OR SPARE PARTS NOT AVAILABLE FOR CRITICAL TREATMENT ITEMS 25 25 R309-525-7(6), R309-525-11(7)(b)(i) and (iii) SIG 120
TD60 CL2 STORAGE OR DAY TANKS NOT PROPERLY VENTED 0 0 TBD REC 0
TD61 CL2 NO PROCESS TO ENSURE CONSISTENT STRENGTH 0 0 TBD REC 0
TD62 NO SAMPLE TAP FOR EACH UNIT OPERATION OF TREATMENT 15 15 R309-535-11(5) MIN 0
TD63 CL2 TANKS OR PIPES NOT USED FOR ONLY 1 CHEMICAL 0 0 TBD REC 0
TD64 CHEMICAL SOLUTION NOT COVERED OR TANK ACCESS OPENINGS NOT COVERED 5 5 R309-525-11(8)(b)(iii) MIN 0
TD65 FACILITY LACKS EMERGENCY EYEWASH AND SAFETY SHOWER 0 0 R309-520-7(3)(a)(i) REC 0
TD66 HYPOCHLORITE FACILITY LACKS A MEANS OF EMERGENCY EYEWASH 25 25 R309-520-7(3)(a)(i) SIG 120
TD67 HYPOCHLORITE LIQUID NOT PROTECTED FROM EXCESSIVE HEAT OR DIRECT SUNLIGHT 5 5 R309-520-7(3)(a)(ii) MIN 0
TD68 NO RECORDS KEPT TO MINIMIZE USE OF DECAYED HYPOCHLORITE SOLUTION 5 5 R309-520-7(3)(b) MIN 0
TD69 INCOMPATIBLE CHEMICALS STORED IN CHLORINE ROOM 25 25 R309-520-7(1)(m) SIG 120
TD70 CHLORINE SOLUTION MAKEUP WATER NOT OF DRINKING WATER QUALITY 25 25 R309-520-7(1)(h)(i), R309-520-7(3)(c)(iii) SIG 120
TD71 HYDROGEN GAS FROM ONSITE HYPOCHLORITE GENERATION ELECTOLYTIC CELL NOT VENTED UPWARD TO OUTSIDE 50 50 R309-520-7(3)(c)(iv) SIG 120
TD72 HYPOCHLORINE TABLETS NOT STORED IN COOL, DRY AND VENTED AREA 5 5 R309-520-7(3)(d)(iii) MIN 0
TD73 HYPOCHLORITE TABLETS STORED WITH COMBUSTIBLE MATERIALS OR ACIDS 25 25 R309-520-7(3)(d)(iii) SIG 120
TD74 PERSONAL PROTECTIVE EQUIPMENT, SAFETY SHOWER OR EYEWASH NOT PROVIDED 25 25 R309-520-10(3)(b)(8) SIG 120
TD75 LACKS SPARE PARTS OR BACKUP EQUIPMENT FOR CHLORINATOR 15 15 Standard Method 334.0 Determination of Residual Chlorine in Drinking Water Using an Online Chlorine Analyzer. [EPA 815-B-09-013 September 2009 11.1.1.2 Page 13] MIN 0
TD76 INADEQUATE MEANS TO MAINTAIN DISINFECTANT RESIDUAL IN THE WATER ENTERING THE DISTRIBUTION SYSTEM 25 25 R309-215-10(2), R309-520-7(1)(c)(iii) SIG 120
TD77 INSUFFICENT SAMPLING FOR CHLORINE RESIDUAL TESTING 0 0 TBD MIN 0
TD78 LACKS EQUIPMENT FOR CHLORINE RESIDUAL TESTING 15 15 R309-520-7(1)(j) MIN 0
TD79 NO MEANS TO MEASURE FLOW RATE OF WATER TREATED 25 25 R309-525-11(7)(d)(ii) and (iii), R309-525-11(7)(a)(i) SIG 120
TD80 CLO2 CHEMICAL NOT PROPERLY STORED EXPLOSIVE 0 0 TBD REC 0
TD81 CLO2 CHEMICAL NOT PROPERLY STORED ALONE 0 0 TBD REC 0
TD82 CLO2 STORAGE STRUCTURE NONCOMBUSTIBLE 0 0 TBD REC 0
TD83 CLO2 STORAGE STRUCTURE NOT NEAR WATER 0 0 TBD REC 0
TD84 CLO2 FEEDERS ARE NOT POS. DISPLACEMNT TYPE 0 0 TBD REC 0
TD85 CLO2 FEED LINES DO NOT STOP AT PT POSITIVE PSI 0 0 TBD REC 0
TD86 CLO2 NO CHECK VALVE BETWEN CL2 & SODIIUM CHLORITE 0 0 TBD REC 0
TD87 CLO2 INSUFFICIENT CONTACT TIME AT APPLICATION PT 0 0 TBD MIN 0
TD88 PRE AND POST CL2 SYS NOT INDEPENDENT-NEEDED TO PREVENT SIPHONING 0 0 R309-525-11(9)(b)(iv) REC 0
TD89 CLO2 INCORRECT RESIDUAL CONC CALCULATION 0 0 TBD REC 0
TD90 ADDING CHEMICALS THAT DO NOT MEET ANSI NSF 60 STANDARD 50 50 R309-525-11(5), R309-520-6(2) SIG 120
TD91 CHLORINATOR LACKS A MEANS TO MEASURE FLOW OF TREATED WATER 25 25 R309-520-7(1)(i) SIG 120
TD92 GAS CHLORINATION EQUIPMENT NOT SECURE OR LACKING PROPER HOUSING 25 25 R309-520-7(2)(f)(i) SIG 120
TD93 1-TON CYLINDER OPERATING AREA LACKS GAS SCRUBBER 25 25 R309-520-7(2)(b) SIG 120
TD94 PRESEDIMENTATION BASINS NOT EQUIPPED FOR SLUDGE REMOVAL 15 15 R309-525-10(1) MIN 0
TD95 GAS CHLORINE ROOM IN TREATMENT PLANT LACKS OUTWARD-OPENING EXIT DOOR WITH PANIC BAR 25 25 R309-520-7(2)(g)(iii) SIG 120
TD96 GAS CHLORINE ROOM IN TREATMENT PLANT HAS FLOOR DRAINS THAT CONNECT TO OTHER DRAINS IN THE PLANT 25 25 R309-520-7(2)(g)(iv) SIG 120
TD97 INSUFFICIENT UV DOSE FOR REQUIRED TREATMENT 25 25 R309-525-8(1)(b)(iv), R309-215-15(19)(d) SIG 120
TD98 LACKS OPERATIONAL RECORDS FOR CHEMICAL DOSING 15 15 R309-105-14(3) MIN 0
TD99 NO MEANS TO MEASURE QUANTITIES OF CHEMICALS USED 25 25 R309-525-11(7)(d)(iv) SIG 120
TF01 FL DOSING NOT CALCULATED OR RECORDED DAILY 15 15 R309-105-14(3) MIN 0
TF02 FL MONITORING AND REPORTING NOT MEETING HEALTH DEPARTMENT REQUIREMENTS 15 15 R309-105-14(3), R309-535-5(1) MIN 0
TF03 FL FACILITY LACKS SECONDARY CONTROL MECHANISM TO PREVENT OVERFEED 50 50 R309-535-5(2)(h) SIG 120
TF04 FL CHEMICAL LACKS ANSI NSF 60 CERTIFICATION 25 25 R309-535-5(2)(a)(i) SIG 120
TF05 FL STORAGE DOES NOT HAVE A VAPOR TRAP 0 0 TBD REC 0
TF06 FL CHEMICAL CONTAINER NOT COVERED OR UNOPENED 15 15 R390-535-5(2)(b)(i) MIN 0
TF07 FLUORIDATION CHEMICALS DO NOT COMPLY WITH ANSI/NSF STANDARDS 0 0 R309-353-5(2)(a)(i) REC 0
TF08 FL MAKE UP WATER NOT TREATED FOR HARDNESS 0 0 R309-535-5(2)(g)(iii) MIN 0
TF09 FL PROCESS WASTES DISCHARGED IMPROPERLY 0 0 TBD REC 0
TF10 EMERGENCY EYEWASH NOT PROVIDED FOR FL SATURATOR OR DRY FEEDER 25 25 R309-535-5(4)(g), R309-535-5(5)(d) SIG 120
TF11 FL NO MEANS TO MEASURE FLOW OF WATER TO BE TREATED 25 25 R309-535-5(2)(d)(i) SIG 120
TF12 INSUFFICIENT FL CRYSTAL AMOUNT IN FL SATURATOR TANK (BELOWED MINIMUM LEVEL MARKED ON OUTSIDE OF SATURATOR TANK) 15 15 R309-535-5(4)(b) MIN 0
TF13 FL FACILITY INADEQUATE PERSONAL PROTECTIVE EQUIPMENT PROVIDED 25 25 R309-535-5(3)(f), R309-535-5(4)(h), R309-535-5(5)(e) SIG 120
TF14 FL NO MEANS TO MEASURE CHEMICAL QUANTITY USED 25 25 R309-535-5(2)(d)(ii) SIG 120
TF15 FL ACID FACILITY LACKS SAFETY SHOWERS AND EYEWASH 25 25 R309-535-5(3)(d) SIG 120
TF16 FLUORIDE INJECTION LINE DOES NOT ENTER IN THE LOWER 1/3 OF WATER PIPE 5 5 R309-535-5(2)(g)(i) MIN 0
TF17 FL INSUFFICIENT OR IMPROPER SAFETY EQUIPMENT 0 0 TBD REC 0
TF18 FL IMPROPER OVERFLOW FROM BULK TANK DAY TANK 15 15 R309-525-11(6)(a)(i)(B) and (iv)(B), R309-535 MIN 0
TF19 FL SATURATOR NOT THE UPFLOW TYPE 0 0 R309-535-5(2)(1) REC 0
TF20 FL LACKS OPERATIONAL RECORDS OF CHEM DOSE AND QUANTITY USED 15 15 R309-105-14(3) MIN 0
TF21 FL TEST EQUIPMENT NOT VERIFIED OR CALIBRATED 15 15 R309-525-25(4) MIN 0
TF22 FL FEED PUMP STARTS WITHOUT WELL OR SERVICE PUMP RUNNING AND WATER FLOWING IN THE PIPE 100 100 R309-535-5(2)(f) SIG 120
TF23 FLUORIDATION EQUIPMENT NOT HOUSED IN SECURE BUILDING 25 25 R309-535-5(2)(h)(i) SIG 120
TF24 FL ACID STORAGE OR INJECTION AREA LACKS VENTING TO OUTSIDE AND AWAY FROM AIR INTAKES 15 15 R309-535-5(2)(j)(iii) MIN 0
TF25 NO SEPERATE SWITCHES FOR FANS AND LIGHTS IN FLUORIDE AREA 15 15 R309-535-5(2)(j)(iv) MIN 0
TF26 FL ACID RESISTANT SPILL CONTAINMENT INADEQUATE OR NOT PROVIDED 25 25 R309-535-5(2)(c )(i), (ii) and (iii) SIG 120
TF27 MAKEUP WATER SUPPLY FOR FL FACILITY LACKS BACKFLOW PROTECTION 50 50 R309-535-5(2)(k), R309-535-5(4)(d) SIG 120
TF28 FL IMPROPER STORAGE OF CHEMICALS 15 15 R309-535-5(2)(b)(i) - (iv) MIN 0
TF29 FL VENTS DO NOT DISCHARGE OUTSIDE ABOVE GRADE 15 15 R309-535-5(3)(b)(ii) MIN 0
TF30 FL ACID FACILITY CONSTRUCTED AFTER JAN 1, 2017 LACKS A VIEW WINDLOW BETWEEN OPERATING AREA AND CONTROL ROOM 15 15 R309-535-5(3)(c) MIN 0
TF31 FL ACID BULK AND DAY TANKS DO NOT HAVE SEPARATE VENTS WHEN BULK TANK OVERFLOW RISK EXISTS 15 15 R309-535-5(3)(b)(iii) MIN 0
TF32 FL ACID FACILITY LACKS A MEANS TO STOP TRANSFER PUMP TRANSFERING ACID FROM BULK TANK TO DAY TANK 0 0 recommendation REC 0
TF33 FL ACID FACILITY LACKS AN EMERGENCY SHUTOFF FOR FL FEED PUMP OR TRANSFER PUMP 0 0 recommendation REC 0
TF34 FL ACID FACILITY LACKS MEANS TO HANDLE CATASTROPHIC FAILURE OF ACID BULK TANK 0 0 recommendation REC 0
TF35 FL ACID FACILITY LACKS SEISMIC RESTRAINT FOR ACID BULK TANK 0 0 recommendation REC 0
TF36 FL DRY CHEMICALS NOT STORED ON PALLETS 5 5 R309-535-5(2)(b)(iii) MIN 0
TF37 FL DISSOLUTION WATER NOT TREATED TO HARDNESS LESS THAN 75 MG/L 15 15 R309-535-5(4)(e)(i) MIN 0
TF38 FL NO NEUTRALIZING CHEMICAL ON SITE 0 0 R309-535-5(3)(e) MIN 0
TF39 FL DRY FEED FACILITY LACKS EXHAUST FAN AND DUST FILTER FOR TRANSFER OF DRY CHEMICALS 15 15 R309-535-5(5)(c)(ii) MIN 0
TF40 FL DRY FEED FACILITY DISCHARGES EXHAUST AIR TO ATMOSPHERE WITHOUT THROUGH DUST FILTER 15 15 R309-535-5(5)(c)(iii) MIN 0
TF41 FL INADEQUATE DISPOSAL OF BAGS, DRUMS OR BARRELS 15 15 R309-535-5(5)(c)(i) MIN 0
TF42 FL NEUTRALIZING CHEMICAL IS NOT AVAILABLE FOR IMMEDIATE USE FOR ACID SPILLS 25 25 R309-535-5(3)(e) SIG 120
TF43 FL SATURATORLACKS A MEANS OF MEASURING QUANTITY OF CHEMICAL SOLUTION USED 25 25 R309-535-5(4)(a) SIG 120
TF44 NO SAMPLE TAP AVAILABLE FOR TESTING FL LEVEL IN TREATED WATER 15 15 R309-535-5(2)(d)(iii) MIN 0
TF45 NO EMERGENCY EYEWASH PROVIDED 0 0 R309-535-5(4)(g) REC 0
TF46 FL SATURATOR NO PERSONAL PROTECTIVE EQUIPMENT AVAILABLE 0 0 R309-535-5(4)(h) REC 0
TF47 FL DRY FEED SOLUTION TANK LACKS MECHANICAL MIXER 15 15 R309-535-5(5)(a) and (b) MIN 0
TF48 FL DRY FEED NO EMERGENCY EYEWASH PROVIDED 0 0 R309-535-5(5)(d) REC 0
TF49 FL DRY FEED NO PROTECTIVE EQUIPMENT AVAILABLE 0 0 R309-535-5(5)(e) REC 0
TF50 INJECTING FLUORIDE UPSTREAM OF LIME SODA SOFTENING, ION EXCHANGE OR OTHER SOFTENING PROCESS 15 15 R309-535-5(2)(g)(iii) MIN 0
TG01 CHEMICAL FEEDERS IMPROPERLY SIZED 0 0 TBD REC 0
TG02 SOLUTION FEEDER LACKS BACKFLOW PROTECTION 0 0 TBD REC 0
TG03 SOLUTION TANKS AND CHEMICAL REFILL LINES NOT LABELED 15 15 R309-525-11(8)(c)(vii) MIN 0
TG04 CHEMICALS ARE STORED IMPROPERLY 0 0 TBD REC 0
TG05 SAFETY DATA SHEET INFO INCLUDEING CHEMICAL NAME, PURITY, CONCENTRATION AND SUPPLIER, NOT AVAILABLE FOR ALL CHEMS 15 15 R309-525-11(5)(a), R309-525-11(6)(b)(i) MIN 0
TG06 SOLUTION TANK LACKS BACKFLOW PROTECTION 0 0 R309-525-11(9)(b)(iii) REC 0
TG07 FEED EQUIPMENT IS NOT OPERABLE 0 0 TBD REC 0
TG08 NO SPARE PARTS AVAILABLE FOR FEEDERS 0 0 R309-525-11(7)(b)(v) REC 0
TG09 NO MEANS TO MEASURE LIQUID LEVEL IN SOLUTION TANK 15 15 R309-525-11(6)(a)(iv)(A), R309-525-11(8)(b)(ii), R309-525-11(8)(c)(iv) MIN 0
TG10 SOLUTION TANK LACKS AN INVERTED J VENT OR A MEANS OF VENTING 5 5 R309-525-11(6)(a)(iv)(C) MIN 0
TG11 FEED EQUIPMENT IS NOT FLOW PACED 0 0 TBD REC 0
TG12 NO ANTISIPHON PROTECTION ON EACH FEED PUMP 0 0 TBD REC 0
TG13 ACID SOLUTION NOT KEPT IN CLOSED ACID-RESISTANT CONTAINERS 15 15 R309-525-11(6)(a)(v) MIN 0
TG14 FEED LINES SUBJECT TO FREEZING 0 0 TBD REC 0
TG15 FEED LINES OF UNAPPROVED MATERIAL 0 0 TBD REC 0
TG16 CHEMICALS NOT FEED IN SEPARATE CONDUITS 0 0 TBD REC 0
TG17 DUST CONTROL AND VENTILATION NOT ADEQUATE FOR HANDLING DRY CHEMICALS 15 15 R309-525-11(6)(c) MIN 0
TG18 SOLUTION TANK NOT PROTECTED AGAINST BACKFLOW OR NOT PROVIDED WITH A VALVED DRAIN 50 50 R309-525-11(8)(b)(vii) SIG 120
TG19 INCOMPATIBLE CHEMICALS ARE FED, STORED OR HANDLED TOGETHER 25 25 R309-525-11(7)(a)(iv) SIG 120
TG20 DAILY RECORDS DO NOT REFLECT DOSAGES ACCURATELY 25 25 R309-105-14(3)(a) SIG 120
TG21 CHEMICAL FEEDERS NOT ACCURATE, CALIBRATED OR FUNCTIONING 25 25 R309-525-11(7)(a)(i) SIG 120
TG22 NO PROVISIONS FOR MEASURING TOTAL CHEMICAL USE 0 0 TBD REC 0
TG25 ACIDS OR CAUSTICS NO STORED PROPERLY 0 0 TBD REC 0
TG26 VENTS DO NOT DISCHARGE OUTSIDE ABOVE GRADE 0 0 TBD REC 0
TG27 CHEMICALS DO NOT COMPLY WITH ANSI/NSF STANDARD 0 0 R309-525-11(5) REC 0
TG31 NO SAMPLE TAP FOR TESTING FINISHED WATER 15 15 R309-525-18, R309-525-25(4) MIN 0
TG32 INADEQUATE PROCESS CONTROL TESTING 0 0 R309-525-19 REC 0
TG34 SW PLANT DOES NOT HAVE CONT RESIDUAL MONITOR 0 0 R309-215-10 REC 0
TG35 CROSS CONNECTION BETWEEN UNTREATED WATER AND FINISHED WATER 50 50 R309-520-7(1)(h), R309-525-11(9)(a) and (b) SIG 120
TG51 NO PROVISIONS FOR DUST CONTROL DURING TRANSFER 0 0 TBD REC 0
TG52 NO PROVISIONS FOR DUST CONTROL DURING DISPOSAL 0 0 TBD REC 0
TG53 NO BACKFLOW PROTECTION ON IN-PLANT WATER SUPPLY LINE 50 50 R309-525-11(9)(b)(i) SIG 120
TG54 NO AIR GAP ON OVERFLOW PIPES 0 0 TBD REC 0
TG56 SUBSURFACE LOCATIONS NOT FREE OF CONTAMINATION 0 0 TBD REC 0
TG57 NO POSITIVE DRAINAGE FOR SUBSURFACE LOCATIONS 0 0 TBD REC 0
TG58 NO LIQUID LEVEL LIMIT SWITCH ON TRANSFER PUMP 0 0 TBD REC 0
TG59 LACKS CONTAINMENT PROVISIONS TO HANDLE SOLUTION TANK SPILLS OR OVERFLOWS 15 15 R309-525-11(6)(a)(iv)(B), R309-525-11(8)(b)(viii) MIN 0
TG60 ACID TANK NOT VENTED TO OUTSIDE 15 15 R309-525-11(8)(b)(vi) MIN 0
TG61 NO MEANS OF MEASURING SOLUTION LEVEL IN TANKS 0 0 TBD REC 0
TG62 IMPROPER DISPOSAL OF PLANT WASTE 0 0 TBD REC 0
TG63 IMPROPER DRY CHEMICAL FEEDER 0 0 R309-525-11(7)(a)(i). REC 0
TG64 IN-PLANT WATER SUPPLY LACKS CROSS CONNECTION CONTROL 50 50 R309-525-11(9)(a)(iii) and (b) SIG 120
TGR1 TRIGGER FOR UNAPPROVED CONSTRUCTION PROJECTS 0 0 TBD 0
TGR2 TRIGGER FOR BACKWASH RECYCLING REVIEW 15 15 R309-215-8 (4) MIN 0
TGR3 TRIGGER FOR UNDOCUMENTED SYSTEM FACILITY OR PROCESS 15 15 R309-105-6 MIN 0
TGR4 TEST KIT VERIFICATION DATES 0 0 TBD 0
TGR5 TOXIC, HAZARDOUS OR FLAMMABLES STORE NEAR SOURCE 0 0 TBD 0
TGR6 CONTACT TIME IN MINUTES FOR CLO2 0 0 TBD 0
TGR7 COM SYSTEM SERVING 100 OR MORE CONNECTIONS LACKS REDUNDANT SOURCE 50 50 R309-515-4(3) SIG 120
TGR8 LOW SPRING FLOW 0 0 TBD 0
TGR9 TRIGGER FOR REGULATORY FOLLOWUP TO ADDRESS CONCERNS 15 15 R309-105-7, 8 & 18, R309-100 through 605 MIN 0
TI01 INHIBITOR ADD - IMPROPER TEST EQUIPMENT 0 0 TBD MIN 0
TI03 INHIBITOR ADD - COMPOUND DOES NOT MEET ANSI/NSF 0 0 TBD SIG 0
TI04 INHIBITOR ADD - CL2 RESIDUALS NOT MAINTAINED 0 0 TBD MIN 0
TI05 POLYPHOSPHATE SEQUESTRATION USED FOR IRON MANGANESE CONTROL WHEN IRON OR MANGANESE OR COMBINATION EXCEEDS 1 MG/L 15 15 R309-535-11(5) MIN 0
TLS1 LIME SODA ASH - NO TEST EQUIP PROVIDED 0 0 TBD MIN 0
TQ01 SEQ - NO TAPS ON EACH PT OF TREATMENT 0 0 R309-535-11(5) MIN 0
TQ02 SEQ - NO TAPS PROVIDED FOR PROCESS CNTRL 0 0 TBD MIN 0
TQ03 SEQ - IMPROPER TEST EQUIPMENT 0 0 TBD MIN 0
TQ04 APPLY POLYPHOSPHATE PRIOR TO IRON MANGANESE TREATMENT OR AFTER AERATION, OXIDATION OR DISINFECTION 15 15 R309-535-11(5)(c ) MIN 0
TQ05 SEQ - IMPROPER POINT OF PHOSPHATE APPLICATION 0 0 TBD MIN 0
TQ06 TOTAL PHOSPHATE APPLIED EXCEEDS 10 MG/L AS PO4 FOR IRON MANGANESE CONTROL 15 15 R309-535-11(5) MIN 0
TQ07 SEQ - STOCK PHOSPHATE SOLUTIONS IMPROPER 0 0 TBD MIN 0
TQ08 LACKS CHLORINE RESIDUAL IN DISTRIBUTION SYSTEM WHEN USING PLOYPHOSPHATE SEQUESTRATION FOR IRON MANGANESE CONTROL 15 15 R309-535-11(5) MIN 0
TQ09 SEQ - CL2 RESIDUALS NOT MAINTAINED 0 0 TBD MIN 0
TQ10 SEQ - POLY SEQUEST CHEMICALS DOES NOT MEET ANSI/NSF STAND 0 0 R309-535-11(5)(d) REC 0
TRG7 HIGH SPRING FLOW 0 0 TBD 0
TRM1 RAPID MIX - SLUDGE IS NOT FED DIRECTLY INTO BASIN 0 0 TBD MIN 0
TS01 SED - CLARIFICATION UNITS REPAIRS DISRUPT OPER 0 0 TBD MIN 0
TS02 SED - SHORT CIRCUITING APPEARS TO OCCUR 0 0 TBD MIN 0
TS03 SED - SIGNIFICANT FLOC CARRYOVER TO FILTERS 0 0 TBD MIN 0
TS08 SETTLERS NOT PROTECTED FROM FREEZING 0 0 TBD MIN 0
TS09 NO FLUSH LINES ON TREATMENT WORKS 0 0 TBD MIN 0
TS10 INSUFFICIENT DETENTION TIME FOR CLARIFIERS 0 0 TBD MIN 0
TS11 SED - CHEMICALS ARE NOT ADDED TO INSURE MIXING 0 0 TBD MIN 0
TS12 SED - MIXING DEVICES DO NOT PROVIDE ADEQUATE MIX 0 0 TBD MIN 0
TS13 SED - MIX DEVICES DO NOT PREVENT IMPROPER DEPOSIT 0 0 TBD MIN 0
TS14 SED - SAMPLE TAPS NOT SUFFICIENT - PROCESS CNTRL 0 0 TBD MIN 0
TS17 SED - NO BACKFLOW PROTECTION ON SLUDGE WASH 0 0 TBD MIN 0
TS19 SED - WATER LOSS EXCEED 5 PERCENT ON CLARIFIERS 0 0 TBD MIN 0
TS20 SED - WATER LOSS EXCEED 3 PERCENT ON SOFTENERS 0 0 TBD MIN 0
TS21 SED - WEIRS ARE NSED - WEIRS ARE NOT ADJUSTABLE OR EQUAL TO TANK 0 0 TBD MIN 0
TT01 TURBIDIMETER NOT CALIBRATED OR MAINTAINED FOR ACCURATE CONTINUOUS MONITORING OF TREATMENT PROCESSES 50 50 R309-525-25(4) SIG 120
TX01 EXCHANGE RESIN DEPTH LESS THAN 3 FEET 0 0 TBD MIN 0
TX02 BACKWASH RATE OUT OF CORRECT 6-8 G/MIN/FT2 RANGE 0 0 TBD MIN 0
TX03 NO MEANS TO CONTROL FLOW RATES 0 0 TBD MIN 0
TX04 NO BACKFLOW PROTECT BACKWSH/RINSE/AIR RELIEF PIPE 0 0 TBD MIN 0
TX05 BRINE SALT NO APPROVED BY ANSI/NSF 0 0 R309-525-11(5)(d) REC 0
TX06 SALT/BRINE TANKS NOT COVERED/CORROSION-RESISTANT 0 0 TBD MIN 0
TX07 NO BACKFLOW PROTECTION ON CHEMICAL MAKEUP WATER SUPPLY LINE 50 50 R309-525-11(2)(c), R309-525-11(9)(b)(i) to (iv) SIG 120
TX08 SOLUTION TANK OVERFLW PIPE NOT DOWNTURNED OR LACKING A CLEARANCE OF 6 INCHES OR MORE 50 50 R309-525-11(8)(b)(v), R309-525-11(9)(b)(iii) SIG 120
TX09 BACKUP OR STANDBY CHEMICAL FEEDER NOT AVAILABLE 15 15 R309-525-11(7)(b)(i) and (ii) MIN 0
TX10 UNSUITABLE DISPOSAL FOR BRINE WASTE 0 0 TBD MIN 0
TX11 SALT SUPPLY IMPROPERLY STORED 0 0 TBD MIN 0
TX15 DESIGN CAPACITY FOR HARDNESS REMOVAL EXCEEDED 0 0 TBD MIN 0
TX16 SOFTENING RATE EXCEEDS 7 GPM PER FT2 OF BED AREA 0 0 TBD MIN 0
TX17 INSUFFICENT SAMPLING TAPS TO EVALUATE TRMT PROCESS 0 0 TBD MIN 0
TX18 NO BYPASS LINE AROUND SOFENING UNITS 0 0 TBD MIN 0
TX19 NO METER ON BYPASS LINE 0 0 TBD MIN 0
TX20 NO SHUT OFF VALVE ON BYPASS LINE 0 0 TBD MIN 0
TX21 NO REGULATING DEVICE ON BYPASS LINE 0 0 TBD MIN 0
V001 STORAGE TANK SURROUNDING AREA NOT GRADED TO PREVENT STANDING WATER WITHIN 50 FEET OF THE TANK 25 25 R309-545-7(4) SIG 120
V002 UNCOVERED FINISHED WATER STORAGE 0 0 R309-545-9(1) REC 0
V003 WATER PONDING ON STORAGE TANK ROOF OR TANK ROOF NOT SLOPED TO DRAIN 15 15 R309-545-9(4) MIN 0
V004 STORAGE TANK LADDERS IN EXCESS OF 20 FEET LACK SAFETY FEATURE SUCH AS CAGE, HARNESS OR PLATFORM 15 15 R309-545-18 MIN 0
V005 STORAGE FACILITY VENT NOT DOWNTURNED AT LEAST 2 INCHES BELOW ANY OPENING 25 25 R309-545-15(1) SIG 120
V006 END OF STORAGE TANK VENT LACKS A CLEARANCE OF AT LEAST 24 INCHES FROM EARTHEN COVER 15 15 R309-545-15(2) MIN 0
V007 STORAGE TANK VENT LACKS NO. 14 SCREEN 25 25 R309-545-15(4) SIG 120
V008 TANK ACCESS HEIGHT LESS THAN 4 INCHES ABOVE TANK ROOF OR LESS THAN 18 INCHES ABOVE EARTHEN COVER 15 15 R309-545-14(1) MIN 0
V009 STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN THE LID AND FRAME 25 25 R309-545-14(2) SIG 120
V010 STORAGE TANK LID NOT SHOEBOX STYLE 25 25 R309-545-14(2) SIG 120
V011 END OF STORAGE TANK OVERFLOW LACKS A CLEARANCE OF BETWEEN 12 AND 24 INCHES FROM GROUND SURFACE 25 25 R309-545-13 SIG 120
V012 END OF STORAGE TANK OVERFLOW PIPE LACKS NO. 4 SCREEN 25 25 R309-545-13(3) SIG 120
V013 STORAGE TANK OVERFLOW PIPE IS CONNECTED TO OR DISCHARGES TO SANITARY SEWER 50 50 R309-545-13(5) SIG 120
V014 STORAGE TANK INTERIOR COATINGS LACKS ANSI NSF 61 CERTIFICATION 25 25 R309-545-21(2) SIG 120
V015 STORAGE FACILITY DRAIN LINE LACKS PROPER SCREEN 0 0 TBD REC 0
V016 END OF TANK DRAIN LINE LACKS A CLEARANCE OF AT LEAST 12 INCHES 25 25 R309-545-10(1)(d) SIG 120
V017 STORAGE TANK SUBJECT TO CONTAMINATION DUE TO UNSEALED OPENINGS ON TANK ROOF OR SIDEWALLS 100 100 R309-545-6(1) and 545-9 SIG 120
V018 STORAGE FACILITY MATERIAL LACKS STABILITY/DURABILITY 0 0 R309-545-6(1) REC 0
V019 STORAGE FACILITY INTERIOR PEELING OR CRACKED 0 0 N/A REC 0
V020 STORAGE FACILITY SHOWS MILD DETERIORATION 0 0 R309-545-9(1) MIN 0
V021 STORAGE TANK ROOF OR SIDEWALLS SHOW SIGNS OF MILD OR MODERATE DETERIORATION 15 15 R309-545-6(1) and 545-9(1) MIN 0
V022 STORAGE TANK ROOF OR SIDEWALLS SHOW SIGNS OF SEVERE DETERIORATION 50 50 R309-545-6(1) and 545-9(1) SIG 120
V023 STORAGE FACILITY IS LEAKING AT TIME OF INSPECTION 0 0 R309-545-9(1) REC 0
V024 STORAGE FACILITY SHOWS EVIDENCE OF WATER INTRUSION 0 0 R309-545-9(1) REC 0
V025 STORAGE TANK WITHIN 50 FEET OF SEWERS OR CONTAMINATION SOURCES 25 25 R309-545-7(3) SIG 120
V026 NO MEANS TO ISOLATE STORAGE TANK FOR O&M 25 25 R309-545-7(5) SIG 120
V027 DRINKING WATER STORAGE TANK SEPERATED FROM WASTEWATER COMPARTMENT BY A SINGLE WALL 50 50 R309-545-9(3) SIG 120
V028 SYSTEM RUNS OUT OF WATER DUE TO STORAGE TANK LACKING LEVEL CONTROL MECHANISM 25 25 R309-545-17 SIG 120
V029 STORAGE TANK ACCESS OPENING LACKS A LOCK 25 25 R309-545-14(3) SIG 120
V030 SYSTEM LACKS UP TO 20% OF REQUIRED STORAGE CAPACITY (FIRE DEMAND NOT INCLUDED) 15 15 R309-510-8 MIN 0
V031 SYSTEM LACKS UP TO 20% OF REQUIRED STORAGE CAPACITY (FIRE DEMAND NOT INCLUDED) 15 15 R309-510-8(1)(a) MIN 0
V032 SYSTEM LACKS MORE THAN 20% OF REQUIRED STORAGE CAPACITY (FIRE DEMAND NOT INCLUDED) 50 50 R309-510-8 SIG 120
V033 SYSTEM LACKS MORE THAN 20% OF REQUIRED STORAGE CAPACITY (FIRE DEMAND NOT INCLUDED) 50 50 R309-510-8 SIG 120
V034 SYSTEM LACKS MORE THAN 20% OF REQUIRED STORAGE CAPACITY (FIRE DEMAND NOT INCLUDED) 50 50 R309-510-8(1)(a) SIG 120
V035 STORAGE TANK VENT LARGER THAN 6 INCHES IN DIAMETER LACKS PROTECTIVE SCREEN 5 5 R309-545-15(5) MIN 0
V036 TANK DRAIN IS CONNECTED OR DISCHRAGES TO A SANITARY SEWER 50 50 R309-545-10(1)(c) SIG 120
V037 STORAGE TANK INTERNAL CATWALKS NOT DESIGNED WITH A SOLID FLOOR AND RAISED EDGES 25 25 R309-545-10(2) SIG 120
V038 STORAGE TANK OVERFLOW DISCHARGE ARE NOT DIRECTED AWAY FROM TANK TO PROTECT TANK FOUNDATION 25 25 R309-545-13 SIG 120
V039 STORAGE TANK ACCESS NOT WATERTIGHT OR NOT SEALED TO PREVENT CONTAMINATION 50 50 R309-545-14(1) and (2) SIG 120
V040 STORAGE TANK VENT NOT SIZED OR LOCATED TO PREVENT BLOCKAGE DURING WINTER 15 15 R309-545-15(3) MIN 0
V041 ELEVATED STORAGE TANK LACKS RAILINGS OR HANDHOLDS 25 25 R309-545-18(3) SIG 120
V042 NO MEANS TO DRAIN A STORAGE TANK FOR O&M 25 25 R309-545-10(1) SIG 120
VF30 SYSTEM LACKS REQUIRED STORAGE CAPACITY DUE TO FIRE DEMAND BUT HAS SOP FOR FOLLOWING FIRE INCIDENT 15 15 R309-510-8 MIN 0
VF31 SYSTEM LACKS REQUIRED STORAGE CAPACITY DUE TO FIRE DEMAND BUT HAS SOP FOR FOLLOWING FIRE INCIDENT 15 15 R309-510-8 MIN 0
VF32 SYSTEM LACKS REQUIRED STORAGE CAPACITY DUE TO FIRE DEMAND BUT HAS SOP FOR FOLLOWING FIRE INCIDENT 15 15 R309-510-8 MIN 0
VF33 SYSTEM LACKS REQUIRED STORAGE CAPACITY DUE TO FIRE DEMAND BUT HAS SOP FOR FOLLOWING FIRE INCIDENT 15 15 R309-510-8 MIN 0
VF34 SYSTEM LACKS REQUIRED STORAGE CAPACITY DUE TO FIRE DEMAND BUT HAS SOP FOR FOLLOWING FIRE INCIDENT 15 15 R309-510-8(1)(b) MIN 0
VF35 SYSTEM LACKS REQUIRED STORAGE CAPACITY DUE TO FIRE DEMAND AND LACKS SOP FOR FOLLOWING FIRE INCIDENT 25 25 R309-105-8(3), R309-510-8(1)(b) SIG 120
VL01 STORAGE TANK LACKS AN OVERFLOW 25 25 R309-545-13 SIG 120
VL02 STORAGE TANK LACKS AN AIR VENT 25 25 R309-545-15 SIG 120
VL03 STORAGE TANK LACKS AN ACCESS OPENING LOCATED ABOVE THE LEVEL OF THE OVERFLOW FOR TANK O&M 15 15 R309-545-14 and 14(1) MIN 0
VL04 STORAGE FACILITY NOT DESIGNED WITH AT LEAST ONE ROOF ACCESS OPENING 0 0 R309-545-14(1) MIN 0
VL05 STORAGE TANK VENT INADEQUATELY SIZED 25 25 R309-545-15 SIG 120